Old Manual Thermostat Installing A New Honeywell Rth7400 Thermostat Cant Get The Heat To Come On?

Installing a new honeywell rth7400 thermostat cant get the heat to come on? - old manual thermostat

The heat and the old thermostat was a manual, but not with the new series

2 comments:

  1. Make sure to be a bridge between RC and RH sure to set the gas / Elec / CV should pins, you must determine the correct position, and finally, we must prepare ourselves that every time the chance of good heat --

    ReplyDelete
  2. Dvdacmn is correct. This (the thermostat setup) must be in the instructions booklet. Anyway, if you have a typical oven (heat pumps are another story), terminal W1 require heat for heating the first phase, which is all he have a gas furnace or oil. Set the thermostat calls for heat, then go to your heater and see if you have 24 volts to terminal W. (between B and C) If yes, then is the problem with the oven, not the t-stat . Note to manage the oven, there's probably a safety switch on the door of the compartment fan, who have all power in the oven when the door is removed to kill, hold on to power and defeat which makes control. In addition, you can inadvertently allowed to change the red wire to the short thermostat? This would probably ensure that the electronic card would be monitoring the air in the oven blew up. Good luck.